How To Repair A Clearstream Septic Timer

SKETCH of a typical aerobic treatment unit tank, aerator, chamber Aerobic Septic System Troubleshooting
Diagnose & fix Problems in Aerobic Septic Systems

  • Mail service a QUESTION or COMMENT nearly problems with the operation of aerobic septic systems

InspectAPedia tolerates no conflicts of interest. Nosotros accept no human relationship with advertisers, products, or services discussed at this website.


Aerobic septic system installation, codes, & trouble diagnosis:

This article discusses bug that occur in aerobic septic systems, too known equally aeration septic systems or fine-chimera septic aerators. We place things that cause problems with or harm aerobic septic systems.

These include flushing chemicals or salt into the aerobic system, electrical bug with the ATU pump or sprayer motors, odors and smells, pipe blockages, sprinkler caput clogs or failures, and other aerobic septic organisation snafus.

At this website are designs and products for aerobic septic handling units (ATUs) for onsite waste disposal, also called fine bubble aeration systems. Nosotros accost aerobic septic system design, features, inspection, repair, and maintenance. Product sources are likewise listed.

Nosotros also provide an ARTICLE Index for this topic, or you can endeavor the page top or lesser SEARCH BOX every bit a quick way to find information yous demand.

Aerobic Treatment Unit Bug

SKETCH of a typical aerobic treatment unit tank, aerator, chamber Commodity Contents

  • AEROBIC ATU SEPTIC Issues
    • DONT FLUSH DRUGS & DISINFECTANTS
    • AEROBIC SEPTIC AERATOR PUMP Issues
    • AEROBIC SEPTIC ALARM SYSTEMS
    • AEROBIC SEPTIC EFFLUENT SPRAY HEAD REPAIR
    • AEROBIC SEPTIC Electric Issues
    • AEROBIC SEPTIC FILTER CLOGGING
    • AEROBIC SEPTIC LIFE EXPECTANCY
    • AEROBIC SEPTIC MAINTENANCE: Clearstream ATUs
    • AEROBIC SEPTIC MAINTENANCE PROCEDURES
    • AEROBIC SEPTIC ODORS & SMELLS
    • AEROBIC SEPTIC OVERLOADING
    • AEROBIC SEPTIC PIPING & BLOCKAGES
    • AEROBIC SEPTIC SALT Bear on on
    • AEROBIC SEPTIC WINTERIZING
    • FROZEN AEROBIC SEPTIC or H2o SUPPLY SYSTEM
    • HOOT AEROBIC SEPTIC TROUBLESHOOTING

Don't Affluent into Aerobic Septic Systems

Drugs: Systems serving homes (or nursing facilities) where occupants are consuming large quantities of medications, particularly antibiotics or perchance chemotherapy drugs, tin be rendered inoperative if the antibiotic or drug level concentration is sufficient to impale the microbes in the ATU.

Disinfectants: Use of improper septic effluent disinfectant in aerobic systems: be sure to use the proper disinfectant in gild to avoid both environmental contamination and violation of federal police.

See AEROBIC Septic Arrangement Disinfection with Calcium Hypochlorite and

AEROBIC Septic Organization Disinfection with Chlorine Tablets for details.

Filter clogging: I take received complaints of frequent outlet filter clogging on someaerobic septic systems. I speculate that the cause may have been a fault in the upstream solid-holding tank(due south) such as a broken or missing baffle, use of the system across its design load, or maybe improper use of hygienic additive or chemic which may have increased the level of suspended solids.

Come across details at AEROBIC SEPTIC FILTER Clogging

Common salt: Systems serving homes with hard water and which apply a water softener can be rendered inoperative ifhigh levels of brine are discharged into the ATU. H2o softener aftermath and brine will need to be discharged to a separate drywell.

Overloading: A residential ATU is at risk of being overloaded and failing to adequately treatits effluent if it has not been properly sized during its design phase.

Aerobic Septic Organization Warning Troubles

Apologies for having to inquire you to "click once more" - for space and clarity nosotros motion this topic.

If you are having problems with the alarm system for an aerobic septic system or ATU alarm delight

see AEROBIC SEPTIC Alarm SYSTEMS where we accept posted a checklist of things to audit, endeavour, or repair.

Aerobic ATU Septic System Electrical Issues

Reader Question: aerobic septic arrangement problems following electrical storm

(June 22, 2022) Db said:
We had an electric storm a few weeks ago and some how the breaker got tripped to entire system. I did not observe this until earlier this week. What problems could I be looking at. I am very regular almost tablets and consistent with not putting damaging products into the organization.

Respond:

Db

I agree that most aerobic septic systems are intended for continual operation. When the aerator pump stops the level of treatment in the tank falls substantially, risking belch of inadequately-treated efflulent into the drainfield. If floating solids are discharged into the fields the field life is reduced as field bottleneck is sped up.

The all-time you can and should do is render the system to proper operation. Don't try extra products or additives, chemicals, treatments unless they are specifically required past the manufacturer of your aerobic system.

Such additives are generally non needed, ineffective, and oft illegal.

Provided your system did not discharge large amounts of solids into the fields you may not see a meaning impact. If you want to be more optimistic or pessimistic y'all could inspect whatsoever distribution boxes or control point downstream from the treatment tank to wait for deposits of solids.

Question: no ability to the ATU pump

(July 30, 2022) christine said:
speedy rooter, the company I have a contract with for my aerobic septic organization did an inspection 3 days agone. They chosen me today and said in that location's no power going to my system and that all three tanks a full.

I checked my circuit breakers and tin can't detect anything amiss, I don't encounter a switch that says septic system either. Speedy Rooter told me I need to get an electrician out here to fix it and so afterwards that I can phone call them to come pump it. The electrician company are saying they tin can get out here in iv days. I'm very nervous well-nigh this. Any advice would be appreciated.

Respond:

Christine

Sounds difficult. I agree with Speedy Rooter. Endeavor calling some more than electricians to discover someone who tin can assist you sooner.

If your system uses an effluent pump operated past a float switch a unproblematic cheque for a stuck bladder could get the system working once again. If not you need an electrician.

Your electrician volition probably check for power at the ATU system pump or effluent pump or sprinkler pump and work backwards to find an open switch, command or circuit.

Aerobic Septic System Aerator Pumps, Effluent Pumps & Pump Command Problems

Loose coupling on air piping at aerobic septic prevents proper aerobic septic operation - how to repair (C) InspectApedia.com BrandiQuestion: loose fittings & air leaks at aerobic septic aerator pipe

2020/01/24 Brandi said:

The circled area in paradigm is loose, non attached on either side, and vibrating vigorously when system is on.

I'grand bold, not allowing air pressure to build.

Reply: repair loose aerobic septic aerator pipe coupling fitting

Brandi

That sounds like a skillful diagnosis of an aerobic septic pump problem - leaky piping, no air pressure level.

The result is bad every bit your system may belch inadequately-treated effluent resulting in an early aerobic septic system failure.

Luckily this isn't a tough problem to fix, with the exception that you might need to movement the aerobic air pump a flake to make room for air line fittings that volition be more than leak and vibration-proof.

In your photo there is a rather short black flexible connector that was probably supposed to isolate the plastic air line from motor vibration.

PVC spring lock compression fitting to stop aerobic septic air piping leaks cited & discussed at InspectApedia.com link to Spears Manufacturing  Too-curt might mean not enough isolation or else even a mechanical stress on the plastic piping that in turn has caused the white PVC compression unions to loosen.

So to gear up this correct you'll need to move the pump a few inches farther away - as it'southward less practical (probably) to movement the vertical air line going down into the aerobic septic tank.

As a very temporary prepare, you could try pushing that right-hand horizontal pipe connexion dorsum into the compression fitting, and then hand tighten the two knurled twist-collars to meet if that fixes the problem.

But over time you will about certainly detect the problem recurrent. There are better PVC compression fittings that are less likely to slip, loosen, and leak.

Plumbing Supply, online at www.plumbingsupply.com/pvccomp.html sells the Griploc™ jump-lock compression fitting that's an example.

This is a more-reliable PVC coupling that volition resist loosening from vibration or from weather exposure and temperature changes.

The instructions and more details about this example of a more-reliable PVC coupling are at

  • PVC COMPRESSION FITTING Griploc Jump-lock [PDF] Spears Manufacturing, 15853 Olden Street, Sylmar, CA 91342 The states, or Spears Manufacturing Canada, PO Box 9203, Sylmar, CA 91392 (818) 364-1611 Website: www.spearsmfg.com

    Doubtless this or similar PVC couplings are also available from your local plumbing supplier.

Reader Question: is it normal for the septic aerator pump to run continuously?

I accept a 4 tank aerobic system that somewhen sprays the treated water, should the aerator pump run 24/7? System serves our single family (merely 2 of us) house. - S.R. 7/17/2013

Respond: normally the septic tank aerator pump should be left running 24/7

Not necessarily.

Some effluent treatment systems that use an above-ground spray arrangement may run under control of a timer. These systems are non normally on all the time.

Some effluent pumping systems that move effluent from a septic tank or effluent tank to an upward-hill effluent disposal system may run under control of an effluent level pump.

Some aerator pumps are designed to run under control of a timer while others are intended to run continuously and further are designed to be quiet and to run rather economically.

In fact since an aerobic septic system depends on aeration to maintain both salubrious aerobic leaner in the septic tank and to clinch adequate wastewater treatment to meet the system operating specifications, y'all should get out the aerator pump on at all times.

Commonly these are small aerobic organisation aeration pumps - about 1/6 to one/3 hp. Some case data near operating toll include:

  • the add-on septic tank aerator pump sold by septicaerator.com draws but about ii amps
  • the septic tank aerator sold by J Jet Wastewater Treatment Systems (jetincorp.com) is a 1/iii hp motor. In discussing typical annual operating price the company says:

    The yearly cost of running an aerator continuously, varies from state to state so depending on what region of the state you live in and the average retail toll of your electricity provider you can expect to pay in the range of $58.78 - $217.25 though in some areas of lower electrical rates (Montana in the U.Due south.) annual aerobic pump costs are between just $12. and $24. USD. [4]

Using the Watts = Amps ten Volts formula (which is technically correct but crude), if your pump is running at 120V AC and draws 2 amps, information technology'due south drawing 240 watts - about the same as a heat lamp, or a typical window fan.

By dissimilarity, an cranium fan draws about 370 watts, and a well pump, about 2,200 watts; or better, comparing with stuff that people leave running 24/7, a 20 cu. ft. automatic-defrosting or frostless refrigerator may draw nigh 800 watts.

Using the constant for converting electric horsepower or hp to watts, 1 hp (electrical, with some simplifying assumptions) = 746 watts.

  • a 1/3 hp 120V electrical septic arrangement aeration pump should draw near 240 W
  • a 1/6 hp 120V electric septic system aeration pump motor should draw about 120 Due west - nigh the same as a 100 watt incandescent lite bulb

Watch out: Just if your pump is noisy or rattling it may need repair or replacement. If you lot'd similar to requite u.s.a. the brand and model of your aerobic system aerator pump nosotros'd be glad to bank check with the manufacturer on this question.

Reader Question: problems with jet aerobic unit of measurement mixer motor

(Sept 18, 2022) Chris said:
I accept a jet aerobics unit of measurement with a mixer. The mixer runs for most 10 minutes, so shuts off. The baffles are sitting relatively close to the mixer, maybe only an inch away.

If the mixer is striking the baffles, would information technology crusade the mixer to shut down? Any other reason it may exist shutting off?

Answer:

Chris, also hitting an obstacle, chock-full outlets or an overheating motor can make the motor shut downward.

Likewise cheque for low voltage, and

see Electrical MOTOR DIAGNOSTIC GUIDE for more than assist.

Reader Question:

(June 27, 2022) Linda said:
Just had a new pump installed and information technology was left for 3 years. I cant become it to pump. Motor is working. Dont know what to do?

Reply:

Pull the pump, cheque it for a clogged inlet or for damaged impeller parts, oe clogged outlet or check valve

Reader Question: no discharge from the aerator pump organisation

(July 17, 2022) Tammy said:

We have an aerator and we never have a belch. We can see the water going in simply never coming out. Can the water or waste product going anywhere else?

Reply:

Tammy,

depending on where yous live and the type of aerobic septic system that has been installed, yeah it is possible for wastewter to be disposed-of entirely below ground.

The "aerator" - if I am guessing correctly at what yous are describing - is in a septic tank in order to increase the level of treatment of the sewage; clarified effluent flows out of the septic tank to a disposal field. Some septic systems spray treated effluent above ground, others merely dispose of it in absorption beds.

(July 17, 2022) Tammy said:

Nosotros take a iii sleeping accommodation air jet system that is in the ground and a pipe that leads to the Creek. It tuckered for 9 years and at present information technology still comes into the get-go chamber but we never see a discharge anymore. Would their still be assimilation beds too? We have no problems otherwise.

Live in KY. Nosotros don't olfactory property anything just practice observe wetness around our brick steps. No other blockages either but like I said the water comes into the tank we can visibly see information technology but we never have a discharge anymore.

Correction information technology goes all the way into the chlorinator. Last chamber.

(July 17, 2022) Tammy said:
We have a system just liken at the meridian of the folio. Jet aerator that leads out to creek for disposing. Nosotros liven in ky. It comes into the 3rd chamber but never leaves a discharge. Information technology utilise to for 9 years. No other bug.

Reply:

Check for a bad float switch on the effluent pump.

Aerobic or ATU Septic Organisation Pipage, Lines, Blockages

Reader Question: we have a blockage in our aerobic lines and never pumped the tank for 12 years. Is the blockage due to the pump?

We have semi-blocked lines and we have a two-chamber ATU and has never had it pumped. Nosotros've lived on this site for 12 years. What can be the problem? Is it a bad pump, or is information technology flood? - Cody 12/1/eleven

Respond:

Short reply: Cody depending on the number of occupants you may accept fallen backside in septic tank pumping frequency

Run into SEPTIC TANK PUMPING SCHEDULE.

If a septic tank is not pumped often enough the take a chance is that the level of treatment falls and solids are pushed into the effluent disposal system causing clogging and sometimes the need for costly repairs. But without opening your system for inspection, one can't accurately gauge farther.

Details: A competent onsite inspection by an expert usually finds additional clues that help accurately diagnose a problem with the septic system. The inspector will need to open the tank, check the operation of the aerator, disinfection arrangement if any, and possibly inspect the effluent disposal organization equally well.

That said, if y'all never pump the septic tank the handling level drops, solids get pushed into the effluent disposal organisation, and the system will first, contaminate the environment with nether-treated effluent and 2d, volition become clogged - that's in general. Of course the specifics for your system will vary.

Y'all'll want your septic contractor to prove y'all the working parts of the system, the maintenance that information technology requires, the maintenance schedule, etc.

Reader Question: broken septic line repair

(Apr 27, 2022) Bearding said:
I take a question, or a possible trouble? On residential site has been on basic well and septic tank, lines busted some 13 ft below and for a distance of another 12 ft, the end of the broken line I ran into the metropolis lines.

Unfortunately for me the pause happened on my side therefore responsible for all costs and excavations of holding not to mention the all the permits, inspections, a lot of red tape. Is this a real possibility for my case or what need answers delight any info anyone could provide would be extremely helpful. Thank you

Reply:

Sorry Anon I don't understand the question. If y'all are asking if truly the property owner is responsible for repairing sewer line breaks on their own property, in most jurisdictions that is indeed the case.

When making repairs ask the plumber and excavator to allow you come across and photograph the actual damage (use our page bottom CONTACT link to find an e-mail to send me some photos for commment). It may be we can discover a cause and avoid some other break in the piping later. For example declining to bed the lines in sand or burying a sharp rock over the line can cause damage.

Reader Question: does an aerobic septic system need to be winterized?

I have recently purchased a new home with an aerobic organisation that has 2 sprinklers. Do I need to winterize the system or turn off the sprinklers in the wintertime? If so, what happens to the water? - Stevi 12/5/xi

Reply:

Stevi an aerobic septic system would be expected to be functional twelvemonth round.

But I agree completely that if your system is installed in a freezing climate, and if information technology uses above-ground effluent spraying, that system cannot work properly in freezing weather. Something sounds wrong with the whole blueprint.

In a climate exposed to freezing the aerobic septic system's piping, pumps, and any controls that pass h2o or effluent demand to be protected from freezing by depth below the frost line or by location in a heated surface area.

Aerobic Septic System Life Expectancy

Reader Question: ATU organization life: My home's septic organisation is 47 years old. Is information technology working correct?

My domicile is 47 years erstwhile, so it would make my 'southward&p' septic organization as as old. I'1000 not sure if that is the correct term for my septic design because information technology is so old. I cannot find a diagram on your website that is comparable to what I think I have.

I have 1 -1000g tank with ane hat, the solid are pumped from this tank. Information technology is continued to a 2nd (1000g) tank, 50 feet away which is a ii story tank. You can stand in upper portion of the 2d tank as it is fabricated of concrete and has a crock hole to the lower function. The bottom portion of the two story tank accumulates liquids coming from the 1st tank.

In one case the liquids in the 2nd lower tank reach a certain level, a sump pump (hanging in the crock) assists in the belch through an underground pipe that is laying on the basis in the woods another 50ft away. Because of its age ("k fathered"), its my septic doing what it is supposed to exist doing? - Kim 4/23/12

Reply:

Kim very few septic systems that are basically untouched for 47 years would lead me, fifty-fifty knowing nothing most them, to opine that the organisation is performing as it should.

The design sounds thoughtful however, as if you have a dosing system = that is, the 2nd effluent tank accumulates effluent in some volume before sending it to an absorption field.

Simply a pipe laying on the ground? That does not sound right at all. Yous didn't depict an aerobic septic organisation (maybe I missed that) and you didn't say in what state you are located, just no where in the U.Due south. or Canada are we permitted to discharge effluent from a septic tank correct onto the ground surface from a distribution pipe such equally you describe.

In some U.S. states it is permitted to use an air spray to distribute effluent that is discharged from an aerobic septic design (tank, aerator, separation baffles, belongings tank or pumping chamber) that is certified to care for effluent to mayhap 95% or better.

But you are not describing such a arrangement. A conventional septic tank treats effluent to a maximum of most 45% of what'southward needed. So you may be discharging sewage onto the ground surface.

Question: Clearstream aerobic system aerator diffuser diaphragm failures & life expectancy

2016/08/10 Rick said:
Bang-up site. Can you tell me how often the diaphragm demand to be replaced on the aerator for a clear stream system? Currently nosotros are having to replace it every two years.

Reply:

Smart question, Rick. I don't know.

I looked at some Articulate Stream literature including the company'south Clearstream ATU Maintenance Guide [PDF] and instructions. world wide web.clearstreamsystems.com/pdf/NC2_Book.pdf
The give-and-take "diaphragm" doesn't fifty-fifty appear in those procedures. However the instructions practise give life expectancies for organization parts including:

"Repair or supercede aerator every 2-10 years". That "repair" could include the aerator diaphragm.

I would check that there's nothing obvious that would reduce the aerator life such as

Clearstream Aerobic Septic ATU Maintenance Checlist

  • Harsh chemicals, acids, solvents, in the septic tank (too search InspectApedia.com

    for TOILETS, DON'T FLUSH LIST - dwelling house for more details)

  • a duty bike that exceeds the design specifications for your system
  • failure to perform ALL of the regular maintenance procedures that Clearstream requires for their arrangement including, for example:
    • make clean the aerator filter every half dozen months to 2 years
    • break up scum in the clarifier every six months to 2 years
    • pump sludge from the aeration tnak every 2-5 years
    • pump sludge from the pre-treatment tank every 2-5 years
    • cheque the aeration diffusers annually
    • check the surge control weir every 6 months
  • Also see AEROBIC ATU SEPTIC MAINTENANCE PROCEDURES

Clearstream expects you to employ a Clearstream agent to inspect and maintain the system - included in the system price for the first 2 years. I'd accept this repair question to that person beginning.

And then I'd contact Clearstream Wastewater Systems to ask their technical support if there'due south something we're missing in this question.

  • Clearstream Wastewater Systems
    PO Box 7658
    Beaumont TX 77726-7568 Usa
    Tel: 409 755 6500
    Website: http://www.clearstreamsystems.com/
    Clearstream ATU Maintenance Guide [PDF]

Odour & Smell Complaints at an Aerobic Septic System ATU

This topic has moved to AEROBIC SEPTIC ODORS & SMELLS

Aerobic Septic System ATU Sprinkler Problems

We have moved this discussion to AEROBIC SEPTIC EFFLUENT SPRAY HEAD REPAIR

Reader Q&A - also come across the FAQs series linked-to below

@Darren Rettie,

I agree with yous completely, it'south often troubling that people invent a organisation, sometimes an expensive one, without the least bit of mutual sense about real-globe weather that their organization is going to encounter.

Sometimes it's because dissimilar engineers in different parts of a project or simply not talking to one another.

I had a Bultaco 360 Montadero Motorbike whose engine was placed into the frame such that the frame blocked the oil pan bleed plug.

The only way to alter the oil required removing whole engine from the frame. Or you might remove the oil fill up plug and plow the motorcycle upside down.

Information technology was completely basics.

Nosotros used to say that the Bultaco engine was designed in Toledo and the frame was made past engineers in Madrid, and the whole motorcycle perhaps was installed in Barcelona

re:
On 2022-01-24 by John

Hiblow HP80 blower working and blowing air out of unit but no bubbles or apportionment in Whitewater DF50. Also, is it normal for the outlet piping of the ATU unit water to sit down 3 inches below the intake? Just had trash and ATU pumped then problems started

I had a like outcome. same set up. No bug with HP eighty, normal op. problem was as installed, at that place is a alarm for low or no air pressure from the HP lxxx, simply not a blockage. our blower was fine, but the bubbler pipage in the tank had some blockage, and likely got worse over the 15 years since install.

Not expert equally the system requires air for proper function. did a retrofit to add a shutoff and a t connector to the 3/4 PVC line earlier it exited our crawlspace to the tank. The t connector I fitted a variety of provisions: to vacuum the line when the tank is drained, an air chuck fitting to blow information technology out, and a water hose valve to flush it out.

As ours silted ( or something) up, and would not aerate at all, I had the tank tuckered and commencement vacuumed the line, used compressed air and finally water to flush. I intend to do this at each pump-out every bit a precaution equally as much as smart engineers designed information technology, they didn't add whatsoever provision to practise this maintenance. For 20 dollars in parts, the omission cost me hundreds in pump-outs. The system is now running every bit designed again.

@Anonymous,

Y'all posted this question and we replied at

http://inspectapedia.com/septic/Aerobic-Septic-Problem-FAQs.php

Will a clog in the inlet chamber not allow effluent or air into next sleeping room causing the tank to overflow at inlet?? Is it possible to accept a clog later the inlet baffle and earlier the effluent reaches the outlet baffle?

@Amos,

Yes, I am concerned that if the aerator is leaking you will non exist pumping sufficient air through the waste material water and information technology volition not be adequately treated.

On my septic system the aerator pipe is leaking air is that pipe supposed to be secure with no air leaks

@Vincelakatos@gmail.com,

No, that does not audio normal to me. I'm a bit worried that you accept overflowing water is running through your plumbing bleed system. If and then and if you continued to subject yourself to field is flooded and non working.

Is it normal to hear your irrigation system running through the pipes in the bathroom if there's flooding exterior in the creek

@Angie,

With Just a smidgen of information I can but guess that your septic organisation is non working properly in that it floods in wet weather.

That condition or the leak point needs to be found - leaks into your septic tank or other bug need to be fixed.

Otherwise your septic organization pushes contaminants into the surroundings.

Information technology may exist that your septic system is not working ordinarily but I can't tell. An inspection of the tank by a professional will tell you if the tank is at normal levels. Information technology could only exist that with the end of weather and your tank on flooded it doesn't need to run the sprayers so oftentimes. Permit usa know what your inspector tells you.

afterward nosotros got a lot of rain it flooded my yard and it was over the top of my Aerobic arrangement and the sprayers would spray evry 10 to 15 minutes Now nosotros havent noticed them spraying at all. What could cause this,why and what practise I demand to do?

@Ella Higgs,

I'm not sure that something is wrong. A lot depends on how much waste product h2o is entering your aerobic system.

If for example you have a running toilet that could exist flooding the aerobic system and setting off the sprinklers.

o start by having someone inspect the septic tank to be sure that there's no water entering information technology when you remember that no waters been running the building. Beyond that check the aerobic timers and controls

Our sprinklers on the aerobic septic system are spraying multiple times per day. What could exist incorrect.

@Joey, do you think in that location could be an air leak, clogged diffuser, kinked tubing, or failing pump? That would explicate why the pump can't button much air into full depth of the aerobic septic tank.

Hi there I have a Clearstream septic system and the aerator does not piece of work when it's fully submerged. It works if it's at one-half superlative? There water seems clean and like shooting fish in a barrel to motion effectually correct to the bottom, the filter is new, the pump is pumping air? What could this problem be? The system was last cleaned and tuckered 6 months ago. Any help would be appreciated

Ted that sounds like a bladder command failure.

My pump that runs the sprinkler does not shut off and when cleans water runs out the dirty water starts to come up out the sprinkler heads.

John

I'm not sure what's going on; if y'all don't have the HiBlow transmission for your system (and its troubleshooting tips) you can download a copy (and also find visitor contact information) in this

HIBLOW HP80 INSTRUCTION MANUAL [PDF] that covers these aerator Models: HP-xl through HP-200

https://inspectapedia.com/septic/Hiblow-Aerator-Pump-manual-HP40-200.pdf

Contact: HIBLOW Us 1300 Tefft Ct. Suite viii, Saline, MI 48176 Tel: 734-944-5032
Email: info@HIBLOW-USA.com

Or if your Hiblow aerobic septic aerator pump is one of the newer models with a slide switch encounter this

HIBLOW HP-SERIES AERATOR Educational activity Manual [PDF]

from the aforementioned source.

Hiblow HP80 blower working and blowing air out of unit merely no bubbling or apportionment in Whitewater DF50. Likewise, is it normal for the outlet pipe of the ATU unit water to sit down 3 inches below the intake? But had trash and ATU pumped so problems started

Tennie

What you depict sounds very odd to me, too. Information technology is just non reasonable to look to have to replace septic pumps so oft, then there is almost certainly something incorrect.

Start your investigation with the pump manufacturer - place the pump make and model, call the manufacturer, and ask

i. are nosotros using the proper pump type and model for our application? And how can nosotros know that the pump is properly or improperly installed? What SNAFUs should nosotros look for?

two. If so, have yous seen this problem before and tin can yous offering an caption and cure?

Practice delight let me know what you're told as that may permit further suggestions from united states of america too.

Beyond that let's wait at the electrical system and pump wiring and grounding:

- the pump wiring and the electrical system grounding; an improper electrical ground ANYWHERE In the electrical system might crusade a current leak (very dangerous, can shock or kill someone) and that in turn tin can too cause surprising corrosion or pinholing; I've seen that in HVAC systems, ground h2o source oestrus pumps, and other pipage installations

The electric concern will be specially truthful if/when you confirm to me that the pump body where the pinholes are developing is metal rather than plastic

We moved in our new home in Oct 2022, and didn't know the Nu Water aerobic septic system was non connected to the quick disconnect box until Jan 2022 when we received inspection. The system failed in March and the pump had to be replaced and once more in May. We had the system pumped out in June. Our maintenance provider no longer wanted to service u.s. then nosotros lost the 2yr warranty. The new provider had to supplant the pump in July and once again in August.

I decided to keep the final 2 pumps and upon closer examination I noticed pinholes in the stainless steel at the lesser of the pump on both. I understand the supplier said he could not award the warranty on the adjacent pump. I have been to the county (Ft Bend ), the country (Texas ) and no one can tell us what the problem is or where to get answers. I accept also noticed the alert on the command panel is very depression and you can barely hear it. I would appreciate any help or advice yous could give us.

Bacteria volition not well enough to brake downward solids have skin of washing pulverization on the surface of the solids

Red lite is on what I need to cheque

Sprinkler heads are non coming on but test lights are working and aerator is working

Loss of electrical ability, a failed pump, or a blockage

What would cause my system to quit spraying

We are getting a sewage smell on the sprinkler heads go off nosotros take plenty of tablets and they are the correct tablets not the pool ones and nosotros take a pump seems to be working as well equally the air compressor putting air in so what would crusade the bad smell or cause it to stop being an aerobic system

Anon

In my Stance if the system was recently spraying (or leaking) sewage effluent onto the ground surface then the elevation layer of soil may include sewage pathogens that every bit dust or mud could be a health risk. It'd be better to requite information technology some fourth dimension. With NO data I'd accept guessed at half-dozen months to be condom.

"In the soil with aerobic conditions, bacteria use for food the organic material that produces the BOD (literally, they pause downwards the BOD and solids, and contain them).

Pathogens are trapped in the soil, either by beingness adsorbed onto soil particles (electrical and chemical interactions betwixt the soil particles and the surfaces of the sewage microbes), or past becoming stuck to the microbial slimes laid downwards by soil bacteria.

One time trapped, some pathogens dice because of unfavorable temperature, lack of wet and food, and other causes. Others are inhibited or killed by antibiotics given off naturally by soil fungi and other organisms.

Yet others are actually preyed upon by soil bacteria and are literally eaten. This process proceeds faster with warmer soil temperatures and slower with cooler temperatures"

- source: Bones PRINCIPLES of ON-SITE SEWAGE SYSTEMS [PDF] Washington Land DOH, retrieved 2022/06/15, original source: https://world wide web.doh.wa.gov/Portals/ane/Documents/Pubs/337-083.pdf

Thanks for the information! Nosotros now take the drainage rerouted and have done abroad with the sprinkler irrigation organisation. Nosotros intend to just make this area office of our k now. Is that ground prophylactic for kids to play on now? Aerator pump was installed later 4.5 months of operating without information technology and the system operated with the aerator pump still with spray irrigation arrangement for i month before the drainage was rerouted to the ditch. Thanks!

Hello. Aerobic system is making a sound but not bustling like normal and it is very hot. The sprinkler heads are not coming up even when you lot push the test button

Ben

Let's start our motor diagnosis past noting where the odor is strongest and whether y'all are xarvio der Outdoors or indoors

Leigh

No, "remediation" of nether-treated-effluent-moisture soils outdoors is non something I've found anyone doing nor recommending other than allowing time - months or longer - for soil bacteria to break down pathogens. Yous may not desire children playing on such an expanse nor would yous plant root crops or low-growing vegetables thereon.

Thanks so much for your reply. Will take to attempt and become information almost the organization from the company that installed information technology, again, to dig further into information technology.

So equally far equally the effluent non be treated - what does that hateful for the ground where the water was spraying for 5 months. Should that expanse be remediated?

Leigh

Those aerobic septic arrangement malfunctions sound really aggravating and disappointing at best. I worry that you only haven't had installation, or repair service, by someone with enough expertise on your particular septic system.

Take a await at the make and model data on your system, its controls, and on any bills or invoices; place the manufacturer, give them a call, and ask for assist.

Finally: there is no aerobic septic arrangement that is designed to operate without its air pump (thus no aerobic or aeration) for months. The result is probable to be clogged distribution piping and spray heads. And of course the effluent being dispersed was not treated.

We have an aerobic sewer system on our home. Our home was completed and nosotros moved in in Dec. Immediately had bug with the float switch not signaling the organisation to boot on then non signaling the system to boot off. The next effect was the olfactory property.

For MONTHS I informed the company that installed the system that the smell was awful and getting worse. The smell was admittedly putrid - just like raw sewage. Finally, 5 months afterward, a technician discovered that the aerator pump was never put on the system.

The aerator pump was put on, it's been a calendar month, and now for the last 2 weeks, the sprinkler heads (spray ideation organisation) accept not been functioning - not spraying and very picayune water coming out. Of the h2o that is coming out, the odour is still awful. I am at my wits terminate with this arrangement.

My question is - due to operating without an aerator pump for 5 months, was the effluence water coming out of the system sanitary? The odour alone leads me to believe it wasn't.

Jennifer

Usually the trouble is a faulty bank check valve nigh the pump or dirty or damaged O-rings in the sprinkler heads.

Have a look and allow me know what you find.

After my sprinklers on my organisation run they go back down but at that place is water just barely trickling out of them and it will not stop! Need answers ASAP! Could they exist faulty?

Yes, Mark,

An aerobic septic system spray head can exist chock-full. Try disassembling and cleaning the unit.

I had to open my air pump and reset the dorsum force per unit area safety switch. I institute that the line going to the aerator is blocked. Probably from ground shifting, I am in Texas later on all. Simply is it possible that the aeration caput has become blocked somehow? The unit of measurement was pumped this past year.

Look for an air leak in the suction line starting time, Joseph.

Hello,
My liquid chlorinator stopped dispensing bleach. I assume line or suction is clogged? All else is working groovy on the system.

Question:

Joleene Duncan

What does the red calorie-free mean

dssaunders said:

I can't get my aerobic system to manually turn on

Respond:

(modern) said: - Aerobic Pump Won't Plough On

I'd start by tracing power to the switch and to the pump;

If you're delivering power to the pump and it'due south not turning on, and if the float switch should be making it run, and if there is power out of the bladder switch, then the pump or pump wire is lacking. Pull the pump and bench exam it.

...

Continue reading at AEROBIC SEPTIC Alarm SYSTEMS - what to do if the septic alarm is sounding, or select a topic from the closely-related articles below, or see the complete ARTICLE Index.

Or run across AEROBIC ATU SEPTIC PROBLEM FAQs - questions & answers posted originally at this folio

Or see these

Recommended Manufactures

  • AEROBIC SEPTIC SYSTEMS, ATUs - home page for Aerobic Septic Systems
  • AEROBIC SEPTIC ALARM SYSTEMS - how to silence & troubleshoot
  • AEROBIC SEPTIC DISINFECTION - Calcium Hypochlorite - Use of calcium hypochlorite tablets for aerobic septic systems
  • AEROBIC SEPTIC EFFLUENT SPRAY HEAD REPAIR
  • AEROBIC SEPTIC FILTER CLOGGING
  • AEROBIC SEPTIC FAILURE RATES, COSTS
  • AEROBIC SEPTIC MAINTENANCE PROCEDURES
  • AEROBIC SEPTIC MAINTENANCE COSTS
  • AEROBIC SEPTIC PROBLEMS
  • AEROBIC SEPTIC PROCEDURES
  • AEROBIC SEPTIC ODORS & SMELLS
  • AEROBIC SEPTIC OPERATING COSTS
  • AEROBIC SEPTIC SYSTEM SUPPLIERS & MANUALS
  • FROZEN AEROBIC SEPTIC or WATER SUPPLY Arrangement
  • HOOT AEROBIC SEPTIC TROUBLESHOOTING
  • SEPTIC System ODOR CURES

Suggested citation for this web page

AEROBIC ATU SEPTIC Issues at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or encounter this

Index to RELATED ARTICLES: Commodity Alphabetize to SEPTIC SYSTEMS

Or apply the SEARCH BOX establish beneath to Ask a Question or Search InspectApedia


...

Ask a Question or Search InspectApedia

Try the search box just beneath, or if y'all prefer, post a question or comment in the Comments box beneath and nosotros will answer promptly.

Search the InspectApedia website

Notation: advent of your Comment below may be delayed: if your comment contains an image, web link, or text that looks to the software equally if information technology might be a web link, your posting volition appear after information technology has been approved by a moderator. Apologies for the delay.

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher InspectApedia.com - Daniel Friedman

Source: https://inspectapedia.com/septic/Aerobic_Septic_Problems.php